Independently developed with fully active maglev bearings, high-speed PMSM motors, high-efficiency internally-threaded tube-bundle heat exchange and adjustable diffuser technologies. Higher energy efficiency, 80 dB noise, and 100 % oil-free operation — for rail transit, schools, hospitals, commercial buildings and process heating.
Request a quote
Model meaning: brand-power (kW). Example: NTCH055 series = NT brand, CH = chiller for heat pump, 55 kW.
| Model | Cooling (kW) | Heating (kW) | ACOP | Length (mm) | Weight ship (kg) |
|---|---|---|---|---|---|
| NTCH100 | 300 | 386 | 6.84 | 3 300 | 3 000 |
| NTCH200 | 576 | 739 | 6.90 | 4 250 | 4 000 |
| NTCH300 | 850 | 1 088 | 6.98 | 4 300 | 5 100 |
| NTCH400 | 1 132 | 1 450 | 7.05 | 4 300 | 5 800 |
| NTCH500 | 1 405 | 1 800 | 7.13 | 4 800 | 6 500 |
| NTCH600 | 1 690 | 2 166 | 7.20 | 4 800 | 7 300 |
| NTCH800 | 2 253 | 2 890 | 7.28 | 5 300 | 9 500 |
| NTCH1000 | 2 818 | 3 613 | 7.38 | 5 800 | 10 600 |
How the maglev heat pump unit stacks up against traditional equivalents.
| Conventional heat pump | Screw heat pump | Maglev heat pump | |
|---|---|---|---|
| Bearings | Oil-lubricated | Oil-lubricated | Active maglev |
| COP | 4.5–5.5 | 5.0–6.0 | up to 7.38 |
| Refrigerant | R134a / R407c | R134a | R134a |
| Noise | > 85 dB | 80–85 dB | ≤ 80 dB |
| Oil-free | No | Partial | 100 % |
| Footprint | Large | Medium | Compact |
| Lifetime | 15 yrs | 20 yrs | 20+ yrs |
COP up to 7.38 for the NTCH1000 model, with COP ≥ 6.84 across the entire NTCH series. The fully active maglev bearing, falling-film shell-and-tube exchanger, and adjustable diffuser all contribute to industry-leading efficiency.
R134a refrigerant, with three-phase 380 V 50 Hz electrical supply. The system includes high-voltage, low-voltage, overload, phase-loss, water-flow, anti-freezing and low-temperature protection.
The NTCH series covers 300 – 2 818 kW rated cooling capacity and 386 – 3 613 kW rated heating capacity, across NTCH100 to NTCH1000 models.
Large commercial and institutional buildings (rail transit, schools, hospitals, hotels), industrial process heating (chemical, papermaking, textile printing & dyeing, rubber & plastics, food, pharmaceutical, biological fermentation), and district energy systems.
Yes. The maglev bearing eliminates lubricating oil completely. This means no oil contamination in the refrigerant loop, no oil change schedule, and improved long-term efficiency.
Send us your flow, pressure and duty cycle — we'll size the right NordicLev unit and return an energy/ROI model within 48 hours.
Talk to an engineer