NTCH Series · 300 – 2 818 kW cooling

COP up to 7.38. Oil-free heating and cooling.

Independently developed with fully active maglev bearings, high-speed PMSM motors, high-efficiency internally-threaded tube-bundle heat exchange and adjustable diffuser technologies. Higher energy efficiency, 80 dB noise, and 100 % oil-free operation — for rail transit, schools, hospitals, commercial buildings and process heating.

Request a quote
7.38
Peak COP
300–2818
kW cooling capacity
R134a
Refrigerant
NordicLev Maglev Heat Pump Unit

Specification types

Model meaning: brand-power (kW). Example: NTCH055 series = NT brand, CH = chiller for heat pump, 55 kW.

ModelCooling (kW)Heating (kW)ACOPLength (mm)Weight ship (kg)
NTCH1003003866.843 3003 000
NTCH2005767396.904 2504 000
NTCH3008501 0886.984 3005 100
NTCH4001 1321 4507.054 3005 800
NTCH5001 4051 8007.134 8006 500
NTCH6001 6902 1667.204 8007 300
NTCH8002 2532 8907.285 3009 500
NTCH10002 8183 6137.385 80010 600

Performance comparison

How the maglev heat pump unit stacks up against traditional equivalents.

Conventional heat pumpScrew heat pumpMaglev heat pump
BearingsOil-lubricatedOil-lubricatedActive maglev
COP4.5–5.55.0–6.0up to 7.38
RefrigerantR134a / R407cR134aR134a
Noise> 85 dB80–85 dB≤ 80 dB
Oil-freeNoPartial100 %
FootprintLargeMediumCompact
Lifetime15 yrs20 yrs20+ yrs
Where it runs

Industries this heat pump serves.

Rail transit Schools Hospitals Commercial buildings Workshops Chemical industry Paper making Textile printing Rubber & plastics Food Pharmaceutical Biological fermentation
Frequently asked questions

About the Maglev Heat Pump.

What COP does the NordicLev heat pump achieve?

COP up to 7.38 for the NTCH1000 model, with COP ≥ 6.84 across the entire NTCH series. The fully active maglev bearing, falling-film shell-and-tube exchanger, and adjustable diffuser all contribute to industry-leading efficiency.

What refrigerant does the NTCH use?

R134a refrigerant, with three-phase 380 V 50 Hz electrical supply. The system includes high-voltage, low-voltage, overload, phase-loss, water-flow, anti-freezing and low-temperature protection.

What is the cooling capacity range?

The NTCH series covers 300 – 2 818 kW rated cooling capacity and 386 – 3 613 kW rated heating capacity, across NTCH100 to NTCH1000 models.

Where is the NTCH heat pump typically used?

Large commercial and institutional buildings (rail transit, schools, hospitals, hotels), industrial process heating (chemical, papermaking, textile printing & dyeing, rubber & plastics, food, pharmaceutical, biological fermentation), and district energy systems.

Is the NTCH heat pump 100 % oil-free?

Yes. The maglev bearing eliminates lubricating oil completely. This means no oil contamination in the refrigerant loop, no oil change schedule, and improved long-term efficiency.

Ready to spec your heat pump?

Send us your flow, pressure and duty cycle — we'll size the right NordicLev unit and return an energy/ROI model within 48 hours.